BOSCH Fire Alarm Panel FPC-500 series

bosch fire alarm jakarta indonesia

FPC-500-2 Fire Alarm Panel 2 Zone, up to 64 Detectors (non batery)
FPC-500-2 Fire Alarm Panel 2 Zone, up to 64 Detectors (include batery)
FPC-500-4 Fire Alarm Panel 4 Zone, up to 128 Detectors (non batery)
FPC-500-4 Fire Alarm Panel 4 Zone, up to 128 Detectors (include batery)
FPC-500-8 Fire Alarm Panel 8 Zone, up to 256 Detectors (non batery)
FPC-500-8 Fire Alarm Panel 8 Zone, up to 256 Detectors (include batery)

LCD with backlight screen and status indication for all detector zones
Self-explanatory icons for intuitive operation
Two history functions with 1,000 entries each, one for events and the other for walk tests
Fully certified according to EN 54, featuring outstanding quality and reliability from Bosch
Autoscroll function for easy checking of the overall panel configuration
High-value modern optics – suitable for public access areas
Plain text LCD
Available for 2, 4 or 8 detector zones for up to 64, 128 or 256 detectors
Optional use of EOL module (EN 54-13 requirement)
Strong 3 A power supply*

BOSCH FPC-500-2, FPC-500-4, FPC-500-8
Input voltage 230 VAC +10%/-15%, 50-60 Hz
Power consumption 80 W
Operating voltage 21.4 VDC to 29 VDC
Imin 70 mA Imax, a 0.7 A Imax, b 2.3 A
Zones
• voltage 20 VDC ±1VDC
• current max. 100 mA ±5 mA
• max. cable resistance 22.5 Ω
AUX
• voltage 21 VDC to 29 VDC
• current 500 mA ±10%
• max. cable resistance 22.5 Ω
• fuse 0.75 A @ 60 V
NAC
• voltage 21 VDC to 29 VDC
• current 500 mA ±10% each
• fuse 0.75 A @ 60 V
• max. cable resistance 22.5 Ω
Relay outputs
• contact rating 1 A @ 30 VDC
• max. cable resistance 22.5 Ω
OC outputs No inductive load.
• contact rating 20 mA @ 24 VDC
• max. cable resistance 22.5 Ω
recommended cable type Unshielded cable, 0.8 mm cable diameter to 1.5 mm² cable cross section
Batteries 2 x 7.2 Ah (max.)*
• max. internal resistance 800 mΩ
• current consumption 2.3 A